160KV/160KVA HV Series AC Resonance Test Device
HV Series AC Resonance Test Device
Product overview
This test device principal for 220KV/25000KVA Main transformer neutral point AC voltage withstand test. The reactor is designed to meet the requirements of low voltage AC voltage test, such as high voltage and low voltage, and it can meet the requirement 10kV cable.
The device is composed of a frequency conversion control power supply, an excitation transformer, a reactor, a capacitor voltage divider, and a compensating capacitor.
HZXB-the manufacturer code
160-the maximum rated capacity of the equipment to be able to output, the unit is kVA
160-the voltage level of the device to be able to output, the unit is kV;
Tech Data
2.2.1. Rated voltage
160kV—Suffice AC withstand voltage test of 220KV/25000KVA Main transformer neutral point AC voltage withstand test; working frequency: 45-65Hz, the test voltage is not more than 160kV, the test time 1min;
2.2.2. Output voltage waveform distortion rate: <>
2.2.3. Allow continuous working time: 60 minutes under the rated conditions;
2.2.4. Device itself quality factor: Q>30
2.2.5. GIS, switch, etc. the full load factor: Q>20(Load related)
2.2.6. Input power: three-phase 380V or single phase 220V
2.2.7. Frequency regulation range: 30Hz-300Hz
2.2.8. System measuring accuracy: 1.5%
2.2.9. The device has the protection function of over voltage, over current and zero position.
Related data
Capacity selection of resonant device
Test current: I=2 PI fCU 10-3 (A)
Frequency selection (HZ)
1, generator -- 50HZ, take 50HZ
2, transformers -- 4565HZ, take 50HZ
3, GIS, switch, bus - - - 30300HZ, take 45HZ
4, power cable: 30300HZ, take 35HZ
Voltage selection (kV)
Determine the maximum test voltage in accordance with the regulations.
Capacitance (UF)
Determine the maximum capacity of the tested product
Maximum capacity: P=UI x 1.25 (kVA)